dc.description.abstractThis paper describes the details for the application of some nontraditional relay curves for the coordination of the ground overcurrent function with downstream fuses. These curves have a segmented shape in order to achieve the best combination of sensitivity, speed, and selectivity. For this segmented shape, greater current does not necessarily imply a shorter time. These curves can be programmed in different ways, according to the available features in the commercial relays, and the expected behavior of two options is analyzed. Both options would have satisfactory behavior although they would have different dynamic behavior.en
dc.format.extent8
dc.identifier.bibliographicCitationE. Sorrentino, "Nontraditional Relay Curves for the Coordination of the Ground Overcurrent Function With Downstream Fuses," in IEEE Transactions on Power Delivery, vol. 29, no. 3, pp. 1284-1291, June 2014, doi: 10.1109/TPWRD.2013.2288134.en
dc.identifier.doihttps://doi.org/10.1109/TPWRD.2013.2288134
dc.identifier.issn0885-8977
dc.identifier.publicationfirstpage1284
dc.identifier.publicationissue3
dc.identifier.publicationlastpage1291
dc.identifier.publicationtitleIEEE Transactions on Power Deliveryen
dc.identifier.publicationvolume29
dc.identifier.urihttps://hdl.handle.net/10016/39673
dc.identifier.uxxiAR/0000034081
dc.language.isoengen
dc.publisherIEEEen
dc.rights© 2014 IEEEen
dc.rights.accessRightsopen accessen
dc.subject.ecienciaElectrónicaes
dc.subject.otherFusesen
dc.subject.otherRelaysen
dc.subject.otherShapeen
dc.subject.otherCircuit breakersen
dc.subject.otherFault currentsen
dc.subject.otherSensitivityen
dc.subject.otherCircuit faultsen
dc.subject.otherGround overcurrent protectionen
dc.subject.otherOvercurrent relay-fuse coordinationen
dc.subject.otherProtection of distribution systemsen
dc.titleNontraditional relay curves for the coordination of the ground overcurrent function with downstream fusesen
dc.typeresearch articleen
dc.type.hasVersionAMen
dspace.entity.typePublication
Files
Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
nontraditional_IEEETPD_2014_ps.pdf
Size:
1.59 MB
Format:
Adobe Portable Document Format